NEW QUESTION 110
The 2.4G antenna on the ECC800 should be installed in ( ).

  • A. RS485 port
  • B. RF_ZA line interface
  • C. 3G/4G antenna interface
  • D. DO output dry contact

Answer: B

 

NEW QUESTION 111
Which of the following are the characteristics of Huawei NetCol5000-A row-level precision air conditioner cooling capacity adjustment?

  • A. DC inverter compressor, which can 20%~100% infinitely adjust cooling capacity.
  • B. When the load is lower than 30%, the compressor starts and stops frequently, and the valve frequently actions and is easily stuck.
  • C. When the load is lower than 20%, the electric heating heat compensation is turned on, and the compressor is continuously operated without stopping.
  • D. Invariable frequency compressor, can't adjust cooling capacity infinitely.

Answer: A,C

 

NEW QUESTION 112
The UPS5000-E accepts input voltage frequency in a range of () Hz.

  • A. 55-65
  • B. 45-70
  • C. 40-70
  • D. 50-60

Answer: C

 

NEW QUESTION 113
Huawei NeCol5000-A row-level precision air conditioner eliminates local hot spots by means of near-end cooling.

  • A. True
  • B. False

Answer: A

 

NEW QUESTION 114
The operation noise of the NetCol5000-A air conditioning unit is abnormal. It should be checked whether the compressor, fan, pipeline, etc. are fixed normally and there is looseness.

  • A. True
  • B. False

Answer: A

 

NEW QUESTION 115
NetCol5000-A air conditioner compressor exhaust temperature is too high, what are the reasons? (Multiple Choice)

  • A. The refrigerant circuit or device is clogged
  • B. condenser filth blockage leads to poor heat dissipation
  • C. Too little refrigerant charge
  • D. The outdoor unit is not installed correctly.

Answer: A,B,C,D

 

NEW QUESTION 116
By setting the mailbox parameters, the NetEco system will send an email to notify the user according to the set rules.

  • A. True
  • B. False

Answer: A

 

NEW QUESTION 117
The multi-function sensor in the Fusion Module2000 modular channel can be connected to the () component.

  • A. Access control actuator
  • B. Cabinet collector
  • C. Smart ETH socket
  • D. WFi converter

Answer: C

 

NEW QUESTION 118
The NetCol5000-A35kW air conditioner has a light load dehumidification function.

  • A. False
  • B. True

Answer: A

 

NEW QUESTION 119
NetEco does not support sending reports to customers by email.

  • A. False
  • B. True

Answer: A

 

NEW QUESTION 120
The NetCol5000-A35kW indoor unit installation needs to be connected to the zero line.

  • A. False
  • B. True

Answer: A

 

NEW QUESTION 121
When the UPS5000-E (), boot will automatically run the Quick Setup Wizard. (Multiple Choice)

  • A. First boot
  • B. Start after recovery failure
  • C. Turn it off and then on.
  • D. The device is turned on again after the factory settings are restored.

Answer: A,D

 

NEW QUESTION 122
After the NetCol5000-A25kW half-cabinet air-conditioning refrigerant pipeline is installed, do the nitrogen charge pressure maintaining, the nitrogen pressure is () Mpa.

  • A. 0
  • B. 1
  • C. 2.5
  • D. 0.8

Answer: B

 

NEW QUESTION 123
If the ECC800 is configured with a SIM card, the SIM card should be installed in ().

  • A. ECC800 main control module left slot
  • B. USB interface
  • C. ECC800 power module slot
  • D. Below the ECC800 antenna port

Answer: A

 

NEW QUESTION 124
Where is the recommended installation location for the Smart ETH socket?

  • A. Side of the cable trough on the top of the cabinet
  • B. Inside the network cabinet
  • C. Control skylight
  • D. Inside the threshold

Answer: A

 

NEW QUESTION 125
Smart ETH sockets support up to () cascading.

  • A. 0
  • B. 1
  • C. 2
  • D. 3

Answer: D

 

NEW QUESTION 126
In order to implement the alarm event remote notification function on NetEco, which of the following tasks need to be set? (Multiple choice)

  • A. Set remote notification rules
  • B. Set the notification server
  • C. Set the notification content template
  • D. Set user groups

Answer: A,B,C,D

 

NEW QUESTION 127
Which of the following components do not support wireless networking?

  • A. Access control actuator
  • B. Skylight actuator
  • C. AC actuator
  • D. ETH converter

Answer: D

 

NEW QUESTION 128
In ECO mode, the UPS operates in the () state when the input is stable.

  • A. Main road inverter
  • B. Maintenance bypass
  • C. Battery
  • D. Bypass

Answer: D

 

NEW QUESTION 129
When the UPS5000-E is installed in parallel, it is not necessary to connect the UPS parallel lines of the parallel system into a loop.

  • A. False
  • B. True

Answer: A

 

NEW QUESTION 130
......